- Thank you for choosing DELTA PLC DVP Series. The analog input module receives external 4-point analog signal input (voltage or current) and converts it into 14 bits digital signal. The analog input module of DVP04AD-S series can read/write the data of analog input module by using instructions FROM/TO via DVP-PLC SS/SA/SX/SC/SV Series MPU program. There are 49 CR (Control Register, each register has 16-bit) in each module.
- The software version of DVP04AD-S analog input module can be updated via RS-485 communication.
Power unit and module are separate. Size is small and easy to install.
- Users can select input from voltage or current via wiring. Voltage input range is +-10VDC (resolution is 1.25mV). Current input range is ±20mA (resolution is 5uA).
Analog/Digital (4A/D) module
Voltage input
Current input
Analog input channel
4 channel/each module
Analog input range
+-10V
+-20mA
Digital conversion range
+-8,000
+-4,000
Resolution
14 bits (1LSB=1.25mV)
13 bits (1LSB=5uA)
Input impedance
> 200KΩ
250Ω
Overall accuracy
+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F)
Isolation method
It has isolation between digital area and analog area. There is no isolation among channels.
Absolute input range
+-15V
+-32mA
Digital data format
2’s complementary of 16-bit, 13 significant bits
Average function
Yes (CR#2 ~ CR#5 can be set and setting range is K1 ~ K4,096)
Self diagnose function
Upper and lower bound detection/channels
Communication mode (RS-485)
Modbus ASCII/RTU Mode. Communication baud rate of 4,800/9,600/19,200/ 38,400/57,600/115,200. For ASCII mode, date format is 7 bits, even, 1 stop bit (7, E, 1), while RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). The RS-485 is disabled when the DVP04AD-S is connected in series with MPU.
Connect to DVP-PLC MPU in series
If DVP04AD-S modules are connected to MPU, the modules are numbered from 0 – 7. 0 is the closest and 7 is the furthest to the MPU. 8 modules is the max and they do not occupy any digital I/O points of the MPU.
Buy Delta PLC Extn Unit Analog module I/O 0/4, DVP04DA-S online in India at wholesale rates. If you have been looking for Delta PLC Extn Unit Analog module I/O 0/4, DVP04DA-S dealers, your search ends here as you can get the best Delta PLC Extn Unit Analog module I/O 0/4, DVP04DA-S distributors in top cities such as Delhi NCR, Mumbai, Chennai, Bengaluru, Kolkata, Chennai, Pune, Jaipur, Hyderabad and Ahmedabad. You can purchase Delta PLC Extn Unit Analog module I/O 0/4, DVP04DA-S of the finest quality and rest assured to get the best in terms of both durability and performance. If you are bothered about the Delta PLC Extn Unit Analog module I/O 0/4, DVP04DA-S prices, you can be totally sure to get the best rates as Industrybuying brings you genuine Delta PLC Extn Unit Analog module I/O 0/4, DVP04DA-S rates and quality assured products only from the best of brands with exclusive brand discounts you won’t find anywhere else. Procure Delta PLC Extn Unit Analog module I/O 0/4, DVP04DA-S today and avail the best offers on your purchase.